Meter Box Switch
Technical Details

VC02SW is an Enclosed Switch Disconnector suitable for Meter Box Applications where an isolating switch between the electricity meter and consumer unit is required.

The twin cable clamps have been additionally proven to secure insulated and sheathed meter tails with conductor sizes ranging from 16-35mm². This greatly reduces the strain on the switch terminals reducing the likelihood of loose electrical connections.

The anti-tamper screw cap is another unique feature of VC02SW, which allows the supply authority to simply secure the main cover in place following installation. The device can also be locked in the open/off position with the appropriate Hager accessory (MZN175).

VC02SW conforms to BS EN 60947-3 which facilitates the installation to comply with BS 7671 IET Wiring Regulations, in particular guidance given in table 53.4.
Dimensions (mm)WidthHeightDepthAB
VC02SW
50
145
78.5
31
109
VC02SW complies with BS EN 60947-3 which facilitates the installation to comply with BS 7671 IET wiring regulations in particular the guidance in table 53.4.
Rated insulation voltage (Ui)
300V
Rated impulse voltage (Uimp)
6kV
Pollution degree
2
Rated duty
Uninterrupted duty
Rated short-time withstand current
1500A/1s
Rated short-circuit marking capacity
2115A
Rated conditional short-circuit (Icc)*
16kA
Type of conductors
Rigid 16/25/35mm²
*Short-circuit protective device: 100A BS 88-3 Fuse. (Fuses mainly for household or similar applications).