Herewith we declare that our products:
Catalogue Number: MTNxx, NBNxxx, NCNxxx, NDNxxx
Trade Mark: Hager
Description MCB
To which this declaration relates, are in conformity to below tables (Breaking capacity, electrical endurance, magnetic tripping level), according to BS/EN 60898-2 in DC applications.
ReferenceNb PoleCurveRatingsVoltage (V)Breaking Capacity (kA)Electrical endurance tests, according to the standard conditions: nb cycles, speed or arming...
MTN1xx
1P
B
0.5 - 63A
60
6 (BS/EN 60898-2, 60947-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
1P
B/C & D
0.5 - 63A
125
10 (BS/EN 60898-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
2P
B/C & D
0.5 - 63A
250
10 (BS/EN 60898-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
3P
B/C & D
0.5 - 63A
250
10 (BS/EN 60898-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
4P
B/C & D
0.5 - 63A
250
10 (BS/EN 60898-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
1P
B/C & D
0.5 - 63A
125
15 (BS/EN 60898-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
2P
B/C & D
0.5 - 63A
250
15 (BS/EN 60898-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
3P
B/C & D
0.5 - 63A
250
15 (BS/EN 60898-2)
1000 cycles
NBNxxx,
NCNxxx,
NDNxxx
4P
B/C & D
0.5 - 63A
250
15 (BS/EN 60898-2)
1000 cycles